New 1PC Thermocouple transfer voltage K type 0-5V 0-10V linear conversion k type temperature transmitter module
K type thermocouple voltage module
This is a linear conversion module with cold-junction temperature compensation that converts the input thermocouple signal to a temperature (voltage signal) output via internal chip processing.
There are two output voltage range options.
Module parameters
1, the working voltage: 9V ~ 17V
2. Input: K type thermocouple
3, the output voltage: 0.00V ~ 5.00V/0.00V ~ 10.00V
4, temperature range: -100 ~ +1100 (degrees).
5. Output method: J1 pad on the circuit board: open circuit (output 0.00V ~ 5.00V); short circuit (output 0.00V ~ 10.00V), the default is open circuit.
6, the scope of application: remote data acquisition and control equipment;
7. Size: (long) 26mm * (width) 23mm * (high) 10mm
8, module interface:
12V: positive power interface (9V ~ 17V).
G: Power ground connector.
I+: Thermocouple positive interface.
I-: Thermocouple negative interface.
OUT: Signal output interface (0.00V ~ 5.00V/0.00V ~ 10.00V).
G: Power ground connector.
Note: When the output is from 0.00V to 10.00V, the power supply voltage must be supplied with 15V.
Output (0.00V ~ 5.00V) Resolution: 0.0041666V/°C (Volts/Celsius)
Output (0.00V ~ 10.00V) Resolution: 0.0083333V/°C (Volts/Celsius)
Calculate the measured temperature equation: (output voltage (V)/resolution) -100°C = measured temperature (°C).